Part Description
Diff Less than 100 ms. If the value is greater than 100 ms, the system maintains the outputs
deactivated.
11.5.10 Restart signal + System recondition (dual channel, redundancy
mode inverted)
Part Description
CH1
CH2
(Restart signal)
Channel 1 of the Restart signal must have a transition of logical level 0 -> 1 -> 0.
Channel 2 of Restart signal must have a transition of logical level 1 -> 0 -> 1. The time
they stay at a high logical level (t) must be at least 200 ms and less than 5 s.
For details about the behavior of Detection signal 1 and 2 outputs and the deactivation
delay, see "Restart signal (dual channel, redundancy mode inverted)" on page126.
CH1
CH2
(System recondition)
Channel 1 of System recondition must have a transition of logical level 0 -> 1 -> 0.
Channel 2 of System recondition must have a transition of logical level 1 -> 0 -> 1. They
must stay at a high logical level (t) for at least 10 s and less than 30 s.
Diff Less than 100 ms. If the value is greater than 100 ms, the system maintains the outputs
deactivated.
11.5.11 Restart signal + System recondition (single channel)
Part Description
Restart signal The channel must have a transition of logical level 0 -> 1 ->0. The time it stays at a high
logical level (t) must be at least 200 ms and less than 5 s.
For details about the behavior of Detection signal 1 and 2 outputs and the deactivation
delay, see "Restart signal (single channel)" on page127.
System recondition The channel must have a transition of logical level 0 -> 1 ->0. The time it stays at a high
logical level (t) must be at least 10 s and less than 30 s.