11.5.13 Dynamic configuration switch (redundancy mode inverted)
With one input
With two inputs
Part Description
Diff Less than 100 ms. If the value is greater than 100 ms, the diagnostic alarm starts and
the system deactivates the safety outputs.
Dynamic
configuration number
For details about the dynamic configuration number and the encoded channels option,
see "Dynamic configuration through the digital inputs" on page35.
Dt Activation/deactivation delay. Less than 50 ms.
11. Technical references
Inxpect SRE 200 Series | Instruction manual v1.5 DEC 2023|Inxpect SAF-IM-200S_5m_7_00047_en_v1.5|© 2021-2023 Inxpect SpA