SETTINGS CONFIGURATION
Settings Confi guration - A pop-up box is pro-
vided to select between the following:
• Disabled – The auxiliary channel will
not be monitored for warnings or shut-
downs.
• When Running - The auxiliary chan-
nel will be monitored for warning and
shutdown occurrences only when the
compressor is in the run state.
• Always - The auxiliary channel will be
monitored for warning and shutdown
occurrences at all times (Running or
not).
The following setpoints are provided for each
Auxiliary Analog channel:
[Low Warning Setpoint] – This setpoint
specifi es the Low Warning alarm threshold.
In the event that the associated auxiliary
analog input falls below this value for a pe-
riod of time exceeding the Low Warning De-
lay, an Auxiliary Low Warning will be issued.
[Low Warning Delay] – This setpoint speci-
fi es the period of time that the associated
auxiliary analog input must remain below
the Low Warning Setpoint before an Auxil-
iary Low Warning will be issued.
[Low Shutdown Setpoint] – This setpoint
specifi es the Low Shutdown threshold. In
the event that the associated auxiliary ana-
log input falls below this value for a period
of time exceeding the Low Shutdown Delay,
an Auxiliary Low Shutdown will be issued,
and the compressor will stop.
[Low Shutdown Delay] – This setpoint
specifi es the period of time that the associ-
ated auxiliary analog input must remain be-
low the Low Shutdown Setpoint before an
Auxiliary Shutdown will be issued.
[High Warning Setpoint] – This setpoint
specifi es the High Warning threshold. In the
event that the associated auxiliary analog
input exceeds this value for a period of time
exceeding the High Warning Delay, an Aux-
iliary High Warning will be issued.
[High Warning Delay] – This setpoint spec-
ifi es the period of time that the associated
auxiliary analog input must remain above
the High Warning Setpoint before an Auxil-
iary High Warning will be issued.
[High Shutdown Setpoint] – This setpoint
specifi es the High Shutdown alarm thresh-
old. In the event that the associated aux-
iliary analog input exceeds this value for a
period of time exceeding the High Shutdown
Delay, an Auxiliary High Shutdown will be is-
sued, and the compressor will stop.
[High Shutdown Delay] – This setpoint
specifi es the period of time that the asso-
ciated auxiliary analog input must remain
above the High Shutdown Setpoint before
an Auxiliary Shutdown will be issued.
NOTE: If you wish to bypass the warnings and
utilize only the shutdown feature, then set all
warning values outside of the shutdown values.