QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 98
CONFIGURATION
Digital Auxiliaries - Timed - Scheduled Control
ACCESSING:
Timed
Scheduled Control
Digital Auxiliaries
DESCRIPTION: This screen may be used to custom as-
sign up to two available digital outputs (A & B) to a timed
schedule:
SCHEDULED DIGITAL OUTPUT CONTROL
Timed Output A - (Off or On status shown)
NOTE: This section is identical for Timed
Output B also.
Control - Three choices are provided:
• Disabled - Output will never
energize (under timed control).
• Running - Output will only be
controlled while the Compressor is
Running.
• Always - The Output will be
controlled all of the time.
Schedule - Two selections are provided:
• Every Day - The Output will be
controlled seven days a week.
• Week Days - The Output will be
controlled Monday through Friday
only.
I/O Board - Three selections are provided:
• None - No board selected.
• Digital Board 1 - The Output to
be controlled is located on Digital
Board 1.
Digital Board 2 - The Output to
be controlled is located on Digital
Board 2.
The following setpoint boxes and drop down
menus are available for Outputs A and B:
On - Enter into these setpoint boxes the
actual time of day that you want the Output
to energize.
Off - Enter into these setpoint boxes the
actual time of day that you want the Output
to de-energize.
I/O Channel - Enter the channel of the
selected Digital Board to control (1 - 24).

Table of Contents