QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 120
CONFIGURATION
Superheat
ACCESSING:
Superheat 1
Superheat Control
DESCRIPTION: The Superheat screens are used to view
and set the operational characteristics of the Superheat
option. Each of the three screens consist of the same lay-
out:
CHANNEL CONFIGURATION
[Name] - A user defi ned name can be entered
here.
[Pressure Input] - A pop-up box is provided to
select from the following input selections:
• Suction Pressure
• Discharge Pressure
• Compressor Oil Pressure
• Main Oil Injection Pressure
• Economizer Pressure
• Filter Pressure
• Intermediate Pressure
• Balance Piston Pressure
• System Discharge Pressure
• Auxiliary Analog #1 - #20
• Manifold Pressure
[Control] - A pop-up box is provided to select
from the following:
• Disabled - No Superheat control.
• Running - Superheat Control only con-
trols when the compressor is running.
• Always - Superheat control always ac-
tive.
[Temperature Input] - A pop-up box is provid-
ed to select from the following input selections:
• Suction Temperature
• Discharge Temperature
• Compressor Oil Temperature
• Oil Separator Temperature
• Process/Brine Temperature Entering
• Process/Brine Temperature Leaving
• Auxiliary Analog 1 - 10
• EZ Cool Feedback %
• Auxiliary Analog 12 - 20
PI CONFIGURATION
[Action] - A pop-up box is provided to select
from the following:
• Forward - Will increase the output at
values greater than the Control Set-
point.
• Reverse - Will increase the output at
values less than the Control Setpoint.
[Setpoint] - A setpoint box is provided to the
value that you wish to control to.