EasyManua.ls Logo

Johnson Controls FRICK QUANTUM HD - Superheat

Johnson Controls FRICK QUANTUM HD
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 120
CONFIGURATION
Superheat
ACCESSING:
Superheat 1
Superheat Control
DESCRIPTION: The Superheat screens are used to view
and set the operational characteristics of the Superheat
option. Each of the three screens consist of the same lay-
out:
CHANNEL CONFIGURATION
[Name] - A user de ned name can be entered
here.
[Pressure Input] - A pop-up box is provided to
select from the following input selections:
• Suction Pressure
• Discharge Pressure
Compressor Oil Pressure
Main Oil Injection Pressure
• Economizer Pressure
• Filter Pressure
• Intermediate Pressure
Balance Piston Pressure
System Discharge Pressure
Auxiliary Analog #1 - #20
• Manifold Pressure
[Control] - A pop-up box is provided to select
from the following:
Disabled - No Superheat control.
Running - Superheat Control only con-
trols when the compressor is running.
Always - Superheat control always ac-
tive.
[Temperature Input] - A pop-up box is provid-
ed to select from the following input selections:
• Suction Temperature
• Discharge Temperature
Compressor Oil Temperature
Oil Separator Temperature
Process/Brine Temperature Entering
Process/Brine Temperature Leaving
Auxiliary Analog 1 - 10
EZ Cool Feedback %
Auxiliary Analog 12 - 20
PI CONFIGURATION
[Action] - A pop-up box is provided to select
from the following:
Forward - Will increase the output at
values greater than the Control Set-
point.
Reverse - Will increase the output at
values less than the Control Setpoint.
[Setpoint] - A setpoint box is provided to the
value that you wish to control to.

Table of Contents

Other manuals for Johnson Controls FRICK QUANTUM HD

Related product manuals