QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 95
CONFIGURATION
Digital Auxiliaries - Digital Aux Outputs
ACCESSING:
A
Digital Aux Outputs
Digital Auxiliaries
DESCRIPTION: Use these screens (Digital Aux. Output A
- J) to setup and control an Auxiliary Digital Output using
the signal from an Analog Input. The following descrip-
tions apply to all Digital Aux. Output pages.
The graphic below illustrates one scenario in which an
analog Temperature input is used to drive a digital output.
When the temperature exceeds the On When value of 75°,
the output will energize. It will remain in this state until
the analog input falls below the Off When value of 73°.
This state will persist until the input again exceeds the
On When value. The resulting temperature control would
resemble the following sine wave:
75°
74
°
73°
76°
72°
Output is
energized
Output is
de-energized
DIGITAL AUX. OUTPUT A - (Off or On status shown)
Analog Input
• Capacity Slide Position
• Volume Slide Position
• Suction Pressure
• Discharge Pressure
• Compressor Oil Pressure
• Main Oil Injection Pressure
• Economizer Pressure
• Filter Pressure
• Intermediate Pressure
• Balance Piston Pressure
• System Discharge Pressure
• Suction Temperature
• Discharge Temperature
• Compressor Oil Temperature
• Oil Separator Temperature
• Process/Brine Temperature Leaving
• Process/Brine Temperature Entering
• Remote Control Setpoint
• Motor Current
• RPM
• User defi ned analog inputs #1 - #20
• User defi ned analog inputs #12 - #20
• Manifold Pressure
• Remote Capacity Position
• Compressor Vibration – Suction
• Compressor Vibration – Discharge
• Motor Vibration – Shaft Side
• Motor Vibration – Opposite Shaft Side