QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 99
CONFIGURATION
Analog Auxiliaries
ACCESSING:
Aux Analog A
Auxiliary Analogs
DESCRIPTION: These screens are used to allow the user
to set the operating safeties of Auxiliary Analog inputs A
through J. The descriptions that follow also apply to the
Auxiliary Analog Input K - T screens also:
CHANNEL CONFIGURATION
The following pop-up menus and setpoint boxes
are provided:
Name - Select this button to enter a custom
name.
[I/O Board] - The following selections are
provided:
• None
Analog Bd 1
Analog Bd 2
[I/O Channel] - A setpoint entry box is
provided to select the analog board output
channel that you wish to use.
[Sensor Output] - The following selections
are provided:
• 0-5V
• 1-5V
• 4-20mA
• ICTD
• 0-20mA
• 0-10V
• 2-10V
SENSOR CONFIGURATION
Current Value - This is the actual value being
read from the sensor at this channel. This is
strictly a displayed value, and cannot be changed
here.
Sensor Type - Select this button to choose the
type of function this sensor is to provide, from
the pop-up menu:
• None
• Pressure
• Temperature
Other (see Units, below)
Units - If the Sensor Type is set to Other (above),
then the applicable Units for the type of sensor
may be entered here. For example, if the Sensor
type is for measuring humidity, select Other for
the sensor type, and enter a percent symbol (%)
for Units.
Low Limit- This will show the low end range that
the sensor is capable of reading.
High Limit - This will show the high end range
that the sensor is capable of reading.