QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 113
CONFIGURATION
PHD Vibration / Temperature - Compressor Bearing Vibration
ACCESSING:
Compressor Bearing
PHD Vibration / Temperature
DESCRIPTION: Use this screen to con gure the Compres-
sor Bearing Vibration. The following setpoint and selec-
tion boxes are provided:
COMPRESSOR BEARING VIBRATION
Compressor Bearing Vibration
• Disabled
• Enabled
[High Warning] - If the Compressor Bearing vi-
bration exceeds this setpoint for the amount of
time as set for the High Warning Delay, then a
Warning is issued.
[High Warning Delay] - The time period as set
here will begin to time down if the Compressor
Bearing vibration exceeds that of the High Warn-
ing, and remains above. When this delay times
out, a Warning will be issued.
[High Shutdown] - If the Compressor Bearing
vibration exceeds this setpoint for the amount
of time as set for the High Shutdown Delay, then
a Shutdown will occur, and the compressor is
stopped.
[High Shutdown Delay] - The time period as set
here will begin to time down if the Compressor
Bearing vibration exceeds that of the High Shut-
down, and remains above. When this delay times
out, a Shutdown will occur, and the compressor
is stopped.
[Sensor Output] - The following selections are
provided:
• 0-5V
• 1-5V
• 4-20mA (If 4-20mA is selected, the
Low Limit and High Limit setpoints will
need entered).
• ICTD
• RTD
• 0-20mA
• 0-10V
• 2-10V
[I/O Board] - The following selections are pro-
vided:
None
Analog Bd 1
Analog Bd 2
[I/O Channel] - A setpoint entry box is provided
to select the analog board output channel that
you wish to use.