QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 159
OIL PUMP STARTING LOGIC
Full Time Pump
(Frick compressor only)
(All pressure calculations are in PSIA)
NOTE: If one of the Other Manufacturer Compressor types, then the Oil Pump must raise the Oil Pressure per
the following calculation before the compressor can start:
Poil-Pdisch > (Low Oil Pressure shutdown + 10 PSI)
If the above calculation is true for 5 seconds, the compressor can start.