QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 109
sequencing ID will be ignored. The lowest IP
address will identify which comp
ressor is
to be the Leader. For example, assume that
there are two compressors in the
sequence order with the following IP
addresses:
116.168.0.141 and 116.168.0.142,
The panel with IP address 116.168.0.141 will
be leader. If the Leader is for some reason
turned off, the next lowest numbered com-
pressor will become the Leader, and so on.
Start # - The allowable numbers here are
0 – 8. This number determines which
compressor to start or stop next, based
upon capacity need. Entering a 0 (zero) in
this field will exclude the compressor from
starting consideration.
Compressor Mode -
• Manual
• Automatic
• Remote Comm
• Remote IO
• Remote Seq.
Capacity Mode -
• Manual
• Automatic
• Remote Comm
• Remote 4-20
• Remote IO
• Remote Seq.
Minimum Capacity - This is the capacity
that a compressor will load to when it is
started. It will remain at or above this ca-
pacity until it is commanded to stop.
NOTE: The Compressor Mode and Capacity
Mode listed above should both be set to Remote
Seq. for complete execution of the
sequencing system by the leader to occur.