QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 115
MOTOR BEARING VIBRATION
Motor Bearing Vibration
• Disabled
• Enabled
[High Warning] - If the amount of vibration ex-
ceeds this setpoint for the amount of time as
set for the High Warning Delay, then a Warning
is issued.
[High Warning Delay] - The time period as set
here will begin to time down if the amount of
vibration exceeds that of the High Warning, and
remains above. When this delay times out, a
Warning will be issued.
[High Shutdown] - If the amount of vibration
exceeds this setpoint for the amount of time as
set for the High Shutdown Delay, then a Shut-
down will occur, and the compressor is stopped.
[High Shutdown Delay] - The time period as
set here will begin to time down if the amount
of vibration exceeds that of the High Shutdown,
and remains above. When this delay times out,
a Shutdown will occur, and the compressor is
stopped.
[Sensor Output] - The following selections are
provided:
0-5V
1-5V
4-20mA
ICTD
RTD
0-20mA
0-10V
2-10V
[I/O Board] - The following selections are pro-
vided:
None
Analog Bd 1
Analog Bd 2
[I/O Channel] - A setpoint entry box is provided
to select the analog board output channel that
you wish to use.