QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 56
be shown:
• Manual
• Automatic
Status - One of the following Statuses will be
shown:
• Idle
• Increase
• Decrease
The following setpoint boxes have been pro-
vided:
• Bottom of Range
• Deadband
• Top of Range
• Minimum On Time
CALIBRATION AREA
The nine buttons in this area allow for calibration
of the Slide Valve and Slide Stop.
The top button functions as follows:
• [Start Calibration] - Selecting this but-
ton will automatically perform all 8 steps
of the manual calibration.
The following group of eight buttons allow for
manually calibrating the Slide Valve and Slide
Stop. These buttons are:
• [Unload Capacity]
• [Set Low Capacity]
• [Increase Volume]
• [Set High Volume]
• [Decrease Volume]
• [Set Low Volume]
• [Load Capacity]
• [Set High Capacity]
To manually calibrate the Slide Valve (capacity) and
Slide Stop (Volume):
• Press the [Unload Capacity] button. Moni-
tor the voltage relative to the Current val-
ue. Once the voltage stops decreasing and
holds steady for 10-15 seconds. Press the
[Set Low Capacity] button.
• Press the [Increase Volume] button. Moni-
tor the voltage relative to the Current Vol-
ume value. When the voltage stops rising
and holds steady for 10-15 seconds. Press
the [Set High Volume] button.
• Press the [Decrease Volume] button. Moni-
tor the voltage relative to the Current val-
ue. Once the voltage stops decreasing and
holds steady for 10-15 seconds. Press the
[Set Low Volume] button.
• Press the [Load Capacity] button. Monitor
the voltage relative to the Current value for
Capacity. When the voltage stops increasing
and holds steady for 10-15 seconds. Press
the [Set High Capacity] button.
OPERATING VALUES
The following informational readings are dis-
played:
Suction
• Temperature
• Pressure
Discharge
• Temperature
• Pressure
Oil
• Temperature
• Pressure
Motor
• Amps