QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 91
pressor Oil Pressure is enabled and
the Oil Pressure is greater than or
equal to this setpoint for the shut-
down delay, the compressor will
shut down.
[Shutdown Delay] - The min-
imum time in seconds that the
Oil Pressure is greater than or
equal to the High Compressor
Oil Pressure Shutdown set-
point before the compressor
will shut down.
TEMPERATURE SAFETIES
Low Oil Separator Temperature
The following setpoint boxes are provided:
[Warning] - If the Oil Separator
Temperature is less than or equal
to this setpoint for the warning
delay, a warning occurs.
[Warning Delay] - The mini-
mum time in seconds that the
Oil Separator Temperature is
less than or equal to the Low
Oil Separator Temperature
Warning setpoint before noti-
cation of the warning.
[Shutdown] - If the Oil Separator
Temperature is less than or equal
to this setpoint for the shutdown
time delay, the compressor will
shut down.
[Shutdown Delay] - The min-
imum time in seconds that the
Oil Separator Temperature is
less than or equal to the Low
Oil Separator Shutdown set-
point before the compressor
will shut down.
Low Comp. Oil Temperature
The following setpoint boxes are provided:
[Warning] - If the Oil Tempera-
ture is less than or equal to this
setpoint for the warning delay, a
warning occurs.
[Warning Delay] - The mini-
mum time in seconds that the
Oil Temperature is less than or
equal to the Low Oil Warning
setpoint before noti cation of
the warning.
[Shutdown] - If the Oil Tempera-
ture is less than or equal to this
setpoint for the shutdown time de-
lay, the compressor will shut down.
[Shutdown Delay] - The min-
imum time in seconds that the
Oil Temperature is less than or
equal to the Low Oil Shutdown
setpoint before the compres-
sor will shut down.
Low Oil Pressure
The following setpoint boxes are provided:
[Warning] - If the Oil Pressure is
less than or equal to this setpoint
for the warning delay, a warning
occurs.
[Warning Delay] - The mini-
mum time in seconds that the
Oil Pressure is less than or
equal to the Low Oil Pressure
Warning setpoint before noti-
cation of the warning.
[Shutdown] - If the Oil Pressure is
less than or equal to this setpoint
for the shutdown delay, the com-
pressor will shut down.
[Shutdown Delay] - The
minimum time in seconds that
the Oil Pressure is less than or
equal to the Low Oil Pressure
Shutdown setpoint before the
compressor will shut down.
High Oil Temperature
The following setpoint boxes are provided:
[Warning] - If the Oil Tempera-
ture is greater than or equal to this
setpoint for the warning delay, a
warning occurs.
[Warning Delay] - The mini-
mum time in seconds that the
Oil Temperature is greater
than or equal to the High Oil
Temperature Warning set-
point before noti cation of the
warning.
[Shutdown] - If the Oil Tempera-
ture is greater than or equal to this
setpoint for the shutdown delay,
the compressor will shut down.
[Shutdown Delay] - The
minimum time in seconds that
the Oil Temperature is greater
than or equal to the High Oil
Temperature Shutdown set-
point before the compressor
will shut down.

Table of Contents

Other manuals for Johnson Controls FRICK QUANTUM HD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls FRICK QUANTUM HD and is the answer not in the manual?

Johnson Controls FRICK QUANTUM HD Specifications

General IconGeneral
BrandJohnson Controls
ModelFRICK QUANTUM HD
CategoryControl Panel
LanguageEnglish

Related product manuals