3-82
SM-18006
TROUBLESHOOTING
Entering Water
Thermistor (THM7)
l
TheRUNindicator(red)ashes.
l
Theindoorunitnumber(refrigerantcyclenumber-addressnumber),thealarmcode,themodelcode
1
,
the model name
1
andthenumberofconnectedindoorunitsaredisplayedontheLCD.Thewater
sourceunitnumberandthealarmcodearedisplayedonthe7-segmentdisplayofthewatersourceunit
PCB.
Note1:Exceptforsomemodels.
Thisalarmcodeisdisplayedwhenashort(0.2kΩorless)oropensensor(840kΩormore)isdetected
duringoperation.
Yes
Yes
Connect them.
No
No
connected to THM7
(Ta, color: red) of
W.S. PCB?
Is resistance of THM7
between 0.2k
Ω
and
840k
Ω
?
Failure of
Thermistor
Failure of W.S. PCB
Refer to "Alarm Code 24"
for thermistor resistance.
Cause Check Item
Action
(Turn OFF Main Switch)
Event
Failure of
Thermistor for
Entering Water
Temp.
Check resistance.
Replace thermistor
if faulty.
Failure
Check wiring to
W.S. PCB.
Repair wiring and
connection.
Incorrect Connection
Replace W.S. PCB
and check operation.
Replace W.S. PCB
if faulty.
Failure of W.S. PCB
W.S.PCB: WaterSourceUnitPCB(PCB1)
Alarm
Code
AbnormalityofThermistorforEnteringWaterTemperature
(WaterSourceUnitEnteringWaterThermistor)