3-26
SM-18006
TROUBLESHOOTING
(E) Alarm Code History Information
This information is indicated at main water source unit (Unit A) only.
If a history of abnormality exists, it is indicated up to a maximum of
15 instances in chronological order.
Press PSW4 (▼) to move forward or PSW2 (▲) to move backward.
Press PSW3 (►) for detailed information.
Press PSW4 (▼) to move forward or PSW2 (▲) to move backward.
Press PSW5 (◄) to return to Data No. Selection.
Display
1 (Latest Data)
15 (Oldest Data)
Data No.
SEG2 SEG1
Item
7-Segment Display
Details
SEG2 SEG1
1
Unit Accumulated
Operation Time
W.S. Accumulated Operation Time at Stoppage
[10 Hours]
2 Cause of Stoppage
Alarm Stoppage
Retry Stoppage
Control Information
3
Alarm Code/
Cause Code of
Stoppage
W.S. No. is indicated on 10 digit of SEG2.
Compressor No. is indicated on
one digit of SEG2.
Alarm and Cause Code of Stoppage are
indicated on SEG1.
4
Abnormal Data
Indication
Cause Code of Inverter Stoppage is indicated
when it is existing on SEG2.
Except for the above.