66 Installation—Installing the FC-2000
Locate Acknowledge, Signal Silence and System Reset switches
adjacent to a system annunciator so that system status is available to
the operator.
Remote Command Circuits are supervised and power limited.
Maximum wire resistance per circuit is 100 ohms. Circuits wired for
Style B operation requires a 4.7K ELR (Part No. 71252) at the end of
the line.
Figure 49: Connection Diagram For Remote Presignal Inhibit,
All Call (General Alarm), Emergency Alert, Acknowledge,
Signal Silence and System Reset Switches (Style B)
Use circuit
D
for All-Call (General Evacuation),
E
for Emergency Alert,
F
for Acknowledge,
G
for Signal Silence, and
H
for Reset.
Style B
B+ B-
izmswtch
4.7K ELR
Part No. 71252
Presignal Inhibit
Switch
Dummy load all
unused circuits with
4.7K, ELR,
Part No. 71245.
INITIATING
ZONE
RED - ALARM
YELLOW- TROUBLE
DISPLAY PROGRAM
MODULE
TYPE
LAMPS
SWITCH
b+b- b+b- b+b- b+b-
A B C D E F G H
b+b- b+b- b+b- b+b-
INITIATING
ZONE
RED - ALARM
YELLOW- TROUBLE
DISPLAY PROGRAM
MODULE
TYPE
LAMP S
SWITC H
A
Presignal Inhibit
B
(Standard Zone)
C
(Standard Zone)
D
(Standard Zone)
E
Emergency Alert
F
Acknowledge
G
Signal Silence
H
Sytem Reset