66 Installation—Installing the FC-2000
● Locate Acknowledge, Signal Silence and System Reset switches
adjacent to a system annunciator so that system status is available to
the operator.
● Remote Command Circuits are supervised and power limited.
Maximum wire resistance per circuit is 100 ohms. Circuits wired for
Style B operation requires a 4.7K ELR (Part No. 71252) at the end of
the line.
Figure 49: Connection Diagram For Remote Presignal Inhibit,
All Call (General Alarm), Emergency Alert, Acknowledge,
Signal Silence and System Reset Switches (Style B)
Use circuit
D
for All-Call (General Evacuation),
E
for Emergency Alert,
F
for Acknowledge,
G
for Signal Silence, and
H
for Reset.
Style B
B+ B-
izmswtch
4.7K ELR
Part No. 71252
Presignal Inhibit
Switch
Dummy load all
unused circuits with
4.7K, ELR,
Part No. 71245.