SECTION 4 - MODBUS RTU SLOT LIST
Modbus DF1 Count Logix Tag Description
10243 N12:8/15 143 AI_PE141A.ALL PRIMARY OIL PUMP PRESSURE VERY LOW
10244 N12:9/0 144 AI_PE141A.AH PRIMARY OIL PUMP PRESSURE HIGH
10245 N12:9/1 145 AI_PE141A.AHH PRIMARY OIL PUMP PRESSURE VERY HIGH
10246 N12:9/2 146 AI_PE141B.OOR SECONDARY OIL PUMP PRESSURE OUT OF RANGE
10247 N12:9/3 147 AI_PE141B.AL SECONDARY OIL PUMP PRESSURE LOW
10248 N12:9/4 148 AI_PE141B.ALL SECONDARY OIL PUMP PRESSURE VERY LOW
10249 N12:9/5 149 AI_PE141B.AH SECONDARY OIL PUMP PRESSURE HIGH
10250 N12:9/6 150 AI_PE141B.AHH SECONDARY OIL PUMP PRESSURE VERY HIGH
10251 N12:9/7 151 AI_PE149A.OOR PRIMARY STALL SENSOR OUT OF RANGE
10252 N12:9/8 152 AI_PE149A.AL PRIMARY STALL SENSOR LOW
10253 N12:9/9 153 AI_PE149A.ALL PRIMARY STALL SENSOR VERY LOW
10254 N12:9/10 154 AI_PE149A.AH PRIMARY STALL SENSOR HIGH
10255 N12:9/11 155 AI_PE149A.AHH PRIMARY STALL SENSOR VERY HIGH
10256 N12:9/12 156 AI_PE149B.OOR SECONDARY STALL SENSOR OUT OF RANGE
10257 N12:9/13 157 AI_PE149B.AL SECONDARY STALL SENSOR LOW
10258 N12:9/14 158 AI_PE149B.ALL SECONDARY STALL SENSOR VERY LOW
10259 N12:9/15 159 AI_PE149B.AH SECONDARY STALL SENSOR HIGH
10260 N12:10/0 160 AI_PE149B.AHH SECONDARY STALL SENSOR VERY HIGH
10261 N12:10/1 161 AI_RST100.OOR REMOTE HARDWIRED SETPOINT OFFSET OUT OF
RANGE
10262 N12:10/2 162 AI_RST100.AL REMOTE HARDWIRED SETPOINT OFFSET LOW
10263 N12:10/3 163 AI_RST100.ALL REMOTE HARDWIRED SETPOINT OFFSET VERY LOW
10264 N12:10/4 164 AI_RST100.AH REMOTE HARDWIRED SETPOINT OFFSET HIGH
10265 N12:10/5 165 AI_RST100.AHH REMOTE HARDWIRED SETPOINT OFFSET VERY HIGH
10266 N12:10/6 166 AI_RST160.OOR REMOTE HARDWIRED DEMAND OFFSET OUT OF
RANGE
10267 N12:10/7 167 AI_RST160.AL REMOTE HARDWIRED DEMAND OFFSET LOW
10268 N12:10/8 168 AI_RST160.ALL REMOTE HARDWIRED DEMAND OFFSET VERY LOW
10269 N12:10/9 169 AI_RST160.AH REMOTE HARDWIRED DEMAND OFFSET HIGH
10270 N12:10/10 170 AI_RST160.AHH REMOTE HARDWIRED DEMAND OFFSET VERY HIGH
10271 N12:10/11 171 AI_TE100.OOR LEAVING CHILLED LIQUID TEMP OUT OF RANGE
10272 N12:10/12 172 AI_TE100.AL LEAVING CHILLED LIQUID TEMP LOW
10273 N12:10/13 173 AI_TE100.ALL LEAVING CHILLED LIQUID TEMP VERY LOW
10274 N12:10/14 174 AI_TE100.AH LEAVING CHILLED LIQUID TEMP HIGH
10275 N12:10/15 175 AI_TE100.AHH LEAVING CHILLED LIQUID TEMP VERY HIGH
10276 N12:11/0 176 AI_TE101.OOR ENTERING CHILLED LIQUID TEMP OUT OF RANGE
10277 N12:11/1 177 AI_TE101.AL ENTERING CHILLED LIQUID TEMP LOW
10278 N12:11/2 178 AI_TE101.ALL ENTERING CHILLED LIQUID TEMP VERY LOW
10279 N12:11/3 179 AI_TE101.AH ENTERING CHILLED LIQUID TEMP HIGH
10280 N12:11/4 180 AI_TE101.AHH ENTERING CHILLED LIQUID TEMP VERY HIGH
10281 N12:11/5 181 AI_TE102.OOR ENTERING CONDENSER LIQUID TEMP OUT OF RANGE
10282 N12:11/6 182 AI_TE102.AL ENTERING CONDENSER LIQUID TEMP LOW
10283 N12:11/7 183 AI_TE102.ALL ENTERING CONDENSER LIQUID TEMP VERY LOW
10284 N12:11/8 184 AI_TE102.AH ENTERING CONDENSER LIQUID TEMP HIGH
10285 N12:11/9 185 AI_TE102.AHH ENTERING CONDENSER LIQUID TEMP VERY HIGH
10286 N12:11/10 186 AI_TE103.OOR LEAVING CONDENSER LIQUID TEMP OUT OF RANGE