FORM 160.77-O2
ISSUE DATE: 11/15/2011
SECTION 3 - YKEP CONTROL PANEL OPERATION
JOHNSON CONTROLS
29
3
Pri Pump Pressure
Displays Display indicates the pressure differential be-
tween the high side oil pressure transducer (primary
compressor) and the low side oil pressure transducer
(oil sump). The displayed value includes offset pres-
sure derived from auto-zeroing during the system
prelube. If either of the transducers used to calculate
this differential are out of range, the display field will
show “+BIG+” (provided by pressure transducers PE-
140 & PE-141A).
Economizer Pump Pressure
Displays Display indicates the pressure differential be-
tween the high side oil pressure transducer (primary
compressor) and the low side oil pressure transducer
(oil sump). The displayed value includes offset pres-
sure derived from auto-zeroing during the system
prelube. If either of the transducers used to calculate
this differential are out of range, the display field will
show “+BIG+” (provided by pressure transducers PE-
140 & PE-141B).
Condenser
Displays the refrigerant pressure in the condenser (pro-
vided by transducer PE-113).
Saturation
Displays the calculated saturation temperature in the
condenser from the pressure (provided by transducer
PE-113).
Condenser Liquid
Leaving
Displays the temperature of the condenser cooling liquid
as it exits the condenser (provided by RTD TE-103).
Return
Displays the temperature of the condenser cooling liquid
as it enters the condenser (provided by RTD TE-102).
Subcooler Temp
Displays the temperature of the refrigerant at the
subcooler (provided by RTD TE-114).
Subcooler Valve
Displays the open percentage of the subcooler level con-
trol valve (provided by actuator feedback LCV-114).
LC114
Displays a proportional graphic of refrigerant liquid
level in the condenser subcooler area. The level per-
centage is also shown numerically, with 0% being
empty and 100% fully flooded sensor.
Sec PRV Position
Displays the open percentage of the Economizer Com-
pressors PRV (provided by feedback potentiometer
ZE-100B).
Sec VGD Position
Displays the open (retracted) position percentage of
the Economizer Compressors VGD (provided by
feedback potentiometer ZE-149B).
Economizer Motor Load
Displays the percentage of FLA utilized by the Econo-
mizer Compressor Motor.
Discharge Temp
Displays the temperature of the refrigerant (vapor) at
discharge of the compressor before the refrigerant en-
ters the Economizer (provided by RTD TE-113).
Run (LED)
Illumates red when the Primary Compressor is cur-
rently running and is grey when off.
Hot Gas
Displays the open percentage of the Hot Gas Bypass
Valve (provided by actuator feedback TCV-100C).
Econ Pressure
Displays the refrigerant pressure in the Economizer
Vessel (provided by transducer PE-116).
Saturation
Displays the calculated saturation temperature in the
Economizer from the pressure (provided by transducer
PE-116).
Target
Displays the target economizer saturation temperature
when the economizer compressor is running.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls York YKEP Series and is the answer not in the manual?

Johnson Controls York YKEP Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYork YKEP Series
CategoryChiller
LanguageEnglish

Related product manuals