KAESER M 64 - Tab. 49 Circuit Breaker; Tab. 50 Generator Operating Limits

KAESER M 64
344 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Type Generator
400V, 3-ph
Generator
230V, 3-ph
Generator
115V, 2-phase
Power sockets Quantity:
16 A; 230 V/3~/PE – 1 –
32 A; 115 V/2~/PE – – 1
16 A; 115 V/2~/PE – – 2
Tab. 48 Connection sockets
Overload protection switch
Type Generator
400V, 3-ph
Generator
230V, 3-ph
Generator
115V, 2-phase
Miniature circuit breaker
[A]
Quantity:
16 1 1 2
32 – 1 1
Tab. 49 Circuit breaker
Operating limits:
(to EN 60034-22, page 10, table)
Features Value
Design category G3
Voltage adjustment range [%] ±5
Static voltage deviation [%] 1
Maximum dynamic voltage drop [%] –15
Maximum dynamic voltage rise [%] 20
Maximum voltage settling time [ms] 1500
Maximum voltage asymmetry [%] 1
Tab. 50 Generator operating limits
Maximum power loading by consumers
Resistive consumers include lamps and heaters, for example.
Electric motors and transformers are inductive consumers.
Nominal rating conditions:
■ Ambient temperature: 25 °C
■ Max. height above sea level at the place of use: 1000 m
2 Technical Specifications
2.8 Options
No.: 9_5898 26 E
Operator manual Portable compressor
M 64