KAESER M 64 - Tab. 57 Circuit Breaker; Tab. 58 Generator Operating Limits; Tab. 59 Maximum Power Supply Load; Tab. 60 Power Reduction at Elevated Ambient Temperatures

KAESER M 64
344 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Overload protection switch
Type Generator
250V, 2-phase
Generator
125V, 1-phase
Miniature circuit breaker
[A]
Quantity:
20 1 1
Tab. 57 Circuit breaker
Operating limits:
(to EN 60034-22, page 10, table)
Features Value
Design category G3
Voltage adjustment range [%] ±5
Static voltage deviation [%] 1
Maximum dynamic voltage drop [%] –15
Maximum dynamic voltage rise [%] 20
Maximum voltage settling time [ms] 1500
Maximum voltage asymmetry [%] 1
Tab. 58 Generator operating limits
Maximum power loading by consumers
Resistive consumers include lamps and heaters, for example.
Electric motors and transformers are inductive consumers.
Nominal rating conditions:
■ Ambient temperature: 25 °C
■ Max. height above MSL of the place of installation: 1,000 m
Generator [kVA] 13.0 8.0
Resistive consum‐
ers [kVA]
per phase 6.5 4.0
total 13.0 8.0
Inductive consumers [kW] Rated power 5.0 5.0
Tab. 59 Maximum power supply load
Power reduction at elevated ambient temperatures:
Ambient temperature
[°C]
Generator power
≤30 Full power available
>30 Reduction of 10 % for each temperature rise of 10 °C.
Tab. 60 Power reduction at elevated ambient temperatures