Functional Description Motor Data and Controller Adjustment
Motor Connection (dr.52) Adjustment of the connection (star/delta).
dr.52 Motor connection
0 star
1 delta (factory setting)
Flux Controller / Mode (CS.22)
With CS.22 the flux controller is changed to max. voltage control. Operation in the
field
weakening range is stabilized by this way. This parameter must only be activated
when the motor parameter adaption is active. The output voltage in the field weakening
range is limited to 100% and a critical increasing is prevented by this.
CS.22 Flow controller / mode
0 Flow controller on (factory setting)
1 Max.voltage controller on (adjustment by Kp)
Adaption factor (dS.15)
Display of the adaption intervention.
Range of values: off (adaption off)
0,1% ... 100,0% (no intervention)