15
ANTRIEBSTECHNIK
6
315
KEB COMBIVERT F4-F
Name: Basis
02.03.99
6
Section PageDate
© KEB Antriebstechnik, 1999
All Rights reserved
Chapter
Functional DescriptionDigital In- and Outputs
Terminal Name Function Decimal value do.0, do.25 u. ru.15
X2.8 Out1 transistor output 1 1
X2.9 Out2 transistor output 2 2
X2.20...22 Out3 relay output 4
- - reserved -
- Out A internal output 16
- Out B internal output 32
- Out C internal output 64
- Out D internal output 128
6.3.17 Inverting of Out-
puts (do.0)
As shown in Fig. 6.3.16 with parameter do.0 the outputs can be inverted. The parameter
is bit-coded, i.e. according to following table the value belonging to the output must
be entered. If several outputs shall be inverted add up the sum.
6.3.18 Output Terminal
Status (ru.15)
The output terminal status indicates the logic condition of the digital outputs. At that it
is irrelevant whether the output is set based on the conditions or through inverting. If
an output is set the corresponding decimal value according to the above table is
displayed. If several outputs are set then the sum of the decimal value is indicated.
Example: Out1 and Out3 to be inverted ➭ 1+4 = 5