KEB COMBIVERT F4-F
6
16.03.99
Fucntional Description
© KEB Antriebstechnik, 1999
All Rights reserved
Chapter Section Page Date
ru-Parameter
3. Fault signals
The reaction of the drive to the fault signals listed below (abnormal stopping) can be determined with parameter Pn.20
and Pn.23...Pn.26:
Display Bus Meaning
A.EF 90 Abnormal Stopping - The signal for an external fault is given to a programmable digital
input.
(reaction of the drive see parameter Pn.20)
A.buS 93 Abnormal Stopping - The adjusted Watchdog-time (parameter ud.8) of the serial
communication was exceeded.
(reaction of the drive see parameter Pn.23)
A.PrF 94 Abnormal Stopping - At setpoint direction forward terminal F (rotation release forward)
Prohibited Rotation is not active.
Forward (reaction of the drive see parameter Pn.24)
A.Prr 95 Abnormal Stopping - At setpoint direction reverse terminal R (rotation release reverse)
Prohibited Rotation is not active.
Reverse (reaction of the drive see parameter Pn.24)
A.dOH 96 Abnormal Stopping - The temperature monitoring of the motor has tripped and the pre-
Drive Overheat warning time (Pn.16) is active.
(reaction of the drive see parameter Pn.25)
A.OH 99 Abnormal Stopping - The temperature monitoring of the frequency inverter has tripped
Overheat and the prewarning time (10 s) is active.
(reaction of the drive see parameter Pn.26)