≥ 130
≥ 250
 *)
≥ 300
D3-DP BG4
D3-DA BG4
*) The bending radius of the connection cables must also be taken into account
Example:
Motor cable 4 x 70 mm
2
 
-> D = 42 mm (for D3-DA 310/x-A3xx)  
(D = outside Ø of the motor cable)
Bending radius (acc. to EN 60332-1-2):
For xed laying   5 x D = approx. 210 mm  
to   7 x D = approx. 292 mm  
depending on the cable type
Figure 3.3  Mounting clearances, KeDrive D3-DA BG4
NOTE: 
It is imperative the min. mounting clearances above and below are met for 
thermal reasons. Depending on the connection cables used (mains cable/
motor cable), the mounting clearances may increase signicantly due to the 
bending radii necessary.
3.3  Cooling of the devices with air cooling 
Cooling air must be able to ow through the device (interior and heat sink) without 
restriction. If a thermal cut-out occurs, the cooling conditions must be improved. 
Note:
Due to the compact design, the 
KeDrive D3 DA axis controllers 
are equipped with internal fans for 
optimal heat dissipation. The speed 
of these fans is set as a function of 
the heat sink temperature. The fan 
noise may therefore vary depending 
on the load.
Figure 3.4  Cooling air ows unhindered through the device
17
1  Mechanical installation 
Operation Manual KeDrive D3-DA BG3 and BG4 
1804.200B.1-01    Date: 03/2023
Mechanical installation