Appendix
A.5 Power reduction at T
unom
≥ 40 °C
If an axis controller is operated outside the specied maximum ambient temperature
(T
unom
), the output power must be reduced as a function of the higher ambient
temperature. This so-called temperature derating is used to protect parts in the device
against overheating.
NOTE:
If the output power is not reduced despite an elevated ambient temperature,
the power stage will shut down due to overtemperature.
Device
Operation without
derating up to T
unom
Operation with derating
up to T
umax
Derating for
T
unom
< T
u
< T
umax
D3-DA 320/x-24xx 40 °C 55 °C
Reduction of the
output power by
4.3% per 1 °C
D3-DA 320/x-32xx 40 °C 55 °C
D3-DA 310/x-45xx 40 °C 55 °C
D3-DA 320/x-45xx 40 °C 55 °C
D3-DA 310/x-80xx 40 °C 55 °C
D3-DA 310/x-A3xx 40 °C 55 °C
Reduction of the
output power by
3.85% per 1 °C
D3-DA 310/x-B1xx 40 °C 55 °C
D3-DA 310/C-C0xx 40 °C 55 °C
Table A.7 Power reduction at T
unom
≥ 40 °C
NOTE:
The derating is to be applied both to the rated currents and to the overload
currents.
NOTE:
Until the type test is completed, all technical data are only calculated values
and not assured characteristics.
A.6 Certications
A.6.1 CE certication
The KeDrive D3-DA axis controllers BG3 and BG4 conform to the requirements of the
Low Voltage Directive 2014/30/EU and the product standard EN61800-5-1.
The KeDrive D3-DA axis controllers BG3 and BG4 thus conform to the requirements
for installation in a machine or plant and are compliant with the Machinery Directive
2006/42/EC.
The KeDrive D3-DA axis controllers BG3 and BG4 are accordingly CE marked.
The CE marking on the rating plate indicates conformity with the above directives.
A.6.2 UL certication
You will nd information about the certication according to UL61800-5-1 for the
KeDrive D3-DA axis controllers BG3 and BG4 in the document "UL-Certication"
ID no.: 0927.02B.x.
A.6.3 Load on the mains due to harmonics
(Note on EN61000-3-2:2006)
The devices in the KeDrive D3 system are "professional equipment" in the context of
EN61000 such that with a nominal connected load ≤ 1kW (or ≤ 16A per mains phase)
they fall within the scope of the standard. If the supply unit ≤1kW is connected directly
to the public low-voltage network, either measures to conform to the standard are to be
taken or the responsible utility must grant approval for connection. If you should use our
drive units as a component in your machine / system, then the scope of the standard is
to be checked for the complete machine / system.