60
1  Commissioning
Operation Manual KeDrive D3-DA BG3 and BG4 
1804.200B.1-01    Date: 03/2023
Commissioning
 KeStudio DriveManager Function
Open manual mode window
Select operation mode
- Initially U/F (open loop)
Motor acceleration
Motor with low speed 
Start motor and check required and actual speed in 
Cockpit (U/F operation)
Start motor control 
Manual mode activated
NOTE:
You will nd further information in relation to "Controlling a drive using 
KeStudio DriveManager" and the manual operation window in the 
KeDrive D3-DA device help (ID no.: 1404.209B.x).
DANGER! Risk of injury due to rotating parts on the motor!
Carelessness may result in serious injuries or death.
Before commissioning motors with feather keys in the shaft end, these keys must be reliably 
secured against throwing out, if this is not already prevented by drive elements such as belt 
pulleys, couplings or similar.
CAUTION! Damage to the motor due to incorrect operation during motor test run!
Carelessness can result in signicant damage to the motor or 
machine.
•  It is imperative the safety instructions and warnings from chapter 2 are followed during 
commissioning. Please note that you yourself are responsible for safe operation.
•  Before you start commissioning it must be ensured that the machine will not be damaged 
by the test! Pay particular attention to the limitations of the positioning range.
•  Certain motors are only intended for operation on the drive controller. Direct connection to 
the mains supply can cause irreparable damage to the motor.
•  The motor surfaces may become extremely hot. No temperature sensitive parts may touch 
or be fastened to these areas, appropriate measures to prevent touching must be taken 
wherever necessary.
•  The temperature sensor installed must be connected to the terminals of the temperature 
monitoring system for the drive controller also during the test run to avoid overheating of 
the motor.
•  The motor holding brake (if installed) should be checked for correct function before 
commissioning the motor. Motor holding brakes are only designed for a limited number of 
emergency braking operations. Use as a service brake is not allowed.
5.3.3  Serial commissioning
Saving the data:
KeStudio DriveManager screen Function
Data set for an individual axis
Data set for the complete device
Data set for an axis group
A saved data set can be transferred to other KeDrive D3-DA axis controllers BG3 and 
BG4 using KeStudio DriveManager. With the aid of the data set for an axis group, 
several devices including the software can be placed in operation. You will nd details in 
the help system in KeStudio DriveManager.