74
1 Appendix
Operation Manual KeDrive D3-DA BG3 and BG4
1804.200B.1-01 Date: 03/2023
Appendix
A.4 Ambient conditions
Ambient conditions KeDrive D3-DA axis controllers BG3 and BG4
Degree of protection Device: IP20 - exception terminals: IP00
Health and safety regulations As per the local regulations (e.g.DGUV V3 in Germany)
Installation altitude
Up to 1000 m aboveMSL, higher with power reduction
(1% per 100m, max. 3000m aboveMSL)
Pollution degree 2 as per EN60664-1
Type of mounting
Built-in unit, only for vertical mounting in a switch cabinet with min. degree of
protection IP4x, if STO safety function used min. IP54
Table A.4 Ambient conditions, KeDrive D3-DA axis controllers BG3 and BG4
Climatic conditions KeDrive D3-DA axis controllers BG3 and BG4
In transit
As per EN61800-2, IEC60721-3-2 class 2K3
1)
Temperature -25°C to +70°C
Relative atmospheric
humidity
95% at max. +40 °C
In storage
As per EN61800-2, IEC60721-3-1 classes 1K3 and 1K4
2)
Temperature -25°C to +55°C
Relative atmospheric
humidity
5 to 95%
In operation
As per EN61800-2, IEC60721-3-3 class 3K3
3)
Temperature 5°C to +40°C (4, 8, 16kHz), to 55°C with power reduction
Relative atmospheric
humidity
5 to 85% without condensation
1) The absolute humidity is limited to max. 60g/m³. This means, at 70°C for example, that the relative atmospheric humidity may only be max. 40%.
2) The absolute humidity is limited to max. 29g/m³. So the maximum values for temperature and relative atmospheric humidity stipulated in the table must
not occur simultaneously.
3) The absolute humidity is limited to max. 25g/m³. That means that the maximum values for temperature and relative atmospheric humidity stipulated in the
table must not occur simultaneously.
Table A.5 Climatic conditions, KeDrive D3-DA axis controllers BG3 and BG4
NOTE:
The climatic conditions apply to the device. For this reason they must also be
met in the switch cabinet.
Mechanical conditions KeDrive D3-DA axis controllers BG3 and BG4
Vibration limit in transit
As per EN61800-2, IEC60721-3-2 class 2M1
Frequency [Hz] Amplitude [mm] Acceleration [m/s²]
2≤f<9 3.5 Not applicable
9≤f<200 Not applicable 10
200≤f<500 Not applicable 15
Shock limit in transit
As per EN61800-2, IEC60721-3-2 class 2M1
Drop height of packed device max. 0.25m
Vibration limits for the
system
1)
As per EN61800-2, IEC60721-3-3 class 3M1
Frequency [Hz] Amplitude [mm] Acceleration [m/s²]
2≤f<9 0.3 Not applicable
9≤f<200 Not applicable 1
1) The devices must not be installed in areas where they are exposed to continuous vibration.
Table A.6 Mechanical conditions, KeDrive D3-DA axis controllers BG3 and BG4
CAUTION! Damage to the device due to incorrect operation!
Failure to observe the ambient conditions may result in damage.
No continuous vibration!
The axis controllers must not be installed in areas where they would be permanently
exposed to vibration.
Switch cabinet min. IP54 for STO and SBC! as per ENISO13849-2
Observe cooling conditions!
NOTE:
The devices are only designed for stationary use.