76
76
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
A0.03
Set the operating
frequency in digital
mode
A0.11~A0.10
0.01Hz
50.00
0~30000
A0.04
Methods of inputting
operating commands
0:Panel control
1:Terminal control
2:Communication control
1
1
0~2
A0.05
Set running
direction
0:Forward
1:Reverse
1
0
0~1
A0.06
Acc time 1
0.0~6000.0
0.1s
2KW or
below:6.0s
30KW~45K
W:20.0s
45KW or
above:30.0s
0~60000
A0.07
Dec time 1
0.0~6000.0
0.1s
2KW or
below: 6.0s
30KW~45KW
20.0s
45KW or
above:30.0s
0~60000
A0.08
Max. output
frequency
upper limit of frequency
A0.11~ 300.00Hz
0.01Hz
50.00
×
0~30000
A0.09
Max. output
voltage
0~480
1V
VFD’s rated
values
×
0~480
A0.10
Upper limit of
frequency
A0.11~A0.10
0.01Hz
50.00
0~30000
A0.11
Lower limit of
frequency
0.00~A0.11
0.01Hz
0.00
0~30000
A0.12
Basic operating
frequency
0.00~Max.output frequency A0.08
0.01Hz
50.00
0~30000
A0.13
Torque boost
0.0%(Auto),0.1%~30.0%
0.1%
0.0%
0~300
Group A1:Start and stop parameters
A1.00
Starting mode
0:Start from the starting
frequency
1:Brake first and then start
2:Start on the fly (including
direction judgement), start at
starting frequency
1
0
×
0~2
A1.01
Starting frequency
0.00~60.00Hz
0.01Hz
0.00Hz
0~6000
A1.02
Holding time of
starting frequency
0.00~10.00s
0.01s
0.00s
0~1000
A1.03
DC injection braking
current at start
0.0%~100.0% drive’s rated current
0.1%
0.0%
0~1000
A1.04
DC injection braking
time at start
0.00(No action)
0.01~30.00s
0.01s
0.00s
0~3000
A1.05
Stopping mode
0:Dec-to-stop
1:Coast-to-stop
2:Dec-to-stop+DC injection braking
1
0
×
0~2
A1.06
DC injection braking
initial frequency at
stop
0.00~60.00Hz
0.01Hz
0.00Hz
0~6000