27 / 89 83000102.Ki
3.27. Remote Control Panel (accessories)
For the case that the chiller shall be operated not from the machine itself but from a different
operating place the chiller can be delivered with a remote control panel. Thereby the same display
is mounted together with the operating voltage supply in one miniature housing. The remote
control panel is connected to the chiller with clips and takes over the complete function of the
controller in the main device. By switching the accordant bridge integrated in the control cabinet,
the required operating place can be chosen.
(in = internally installed control / out = outward leading control)
3.28. Special languages (accessories)
These instruction manuals are provided in German, English, French and Spanish. Other languages
are available on request.
3.29. Wooden Crate (accessories)
Whereas the chillers of the Compact-Line are delivered on a wooden palette with Styrofoam
corners stretched in the foil as a standard, the chillers can be also ordered in a wooden crate.
There the chillers are protected additionally by a wooden crate with IPPC-Label according ISPM
15.
3.30. Seaworthy crate packaging (accessories)
Seaworthy crates for the Compact-Line are produced according to International Standards for
Phytosanitary Measures with packaging made of solid wood (ISPM 15). This means that the
crates are made of heat-treated solid wood which has been stripped of its bark. Only wood-based
materials, such as OSB boards, are used. In addition, all crates are marked with the IPPC logo
and registration number. The units are fixed in the crate with the help of coach bolts, ring nuts
and polyester straps and are packed in a sea air consistent foil with desiccant. The components
used to pack the units can be dismantled using a cross-head screwdriver.
3.31. Water Pump Redundancy
Depending on the optional configuration, the cboxX (water chiller) can be equipped with a dual
water pump for redundancy and increased life time of the pump itself. The operating hours of the
pumps are programmable and can be shared by both pumps (f. e. 24h switch on/off between
both pumps). In case of a pump defect, an automatic switch to the pump redundant, ensures the
continuation of the water chiller and the operation of the end customers application.
3.32. Closed Water Loop
The water chiller is designed as a closed water loop system with an expansion tank. The
expansion tank is pressurized in accordance with the volume of the entire system volume
(including installation). The expansion tank balances temperature swings and related system
pressure of the water loop. In case the coolant temperature rises the expansion tank takes in the
expanded volume of the coolant and if the coolant temperature falls the stored volume will be
released back into the loop again.
Advantages of a closed water loop system are: