82 / 89 83000102.Ki
382
386
Pumppress.1 min STOP
Pumppress.2 min STOP
Liquid outlet pressure too
low
Flow rate too high, chiller
resistance too low,
air in the system
Reduce flow rate,
increase chiller
resistance, vent the
system
501
AI inlet temp. (VP)
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
502
AI outlet temp.
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
503
AI outlet temp. 2
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
504
AI temp.system return
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
505
AI ambient temp.
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
506
AI freecooler temp inlet
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
511
AI CW press. evap.
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
512
AI press exp.tank
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
513
AI pump press. 1
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
514
AI pump press. 2
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
515
AI tank pressure
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
521
AI high pressure
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
522
AI low pressure
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
523
AI suction gas temp.
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor