41 / 89 83000102.Ki
4.11. Information for emergencies
If an emergency occurs during operation of the chiller the machine must be disconnected from
the mains at once using the master switch. Remove people from the danger zone immediately. An
emergency situation can among other things be:
o a leak and escape of refrigerant and/ or oil.
o a part of the machine becoming mechanically detached from it.
o the machine making unusual noises.
o the machine vibrating severely.
Then contact the KKT chillers Service Team. If you detect a refrigerant or oil leak, proceed as
described in Chapter 4.9 Dangerous substances.
5. Handling and storage
The chiller is fixed on a wooden pallet in the factory for delivery. The machine is additionally
protected against damage by polystyrene corner protectors and stretch film. Therefore you should
remove the packaging as late as possible.
5.1. Dangerous goods
Chillers with refrigerant capacity >12 kg must be declared as dangerous goods in accordance
with UN2857. The cBoxX 30 – cBoxX 100 chillers have been specified so that they contain <12
kg refrigerant. The cBoxX 120 – cBoxX 200 chillers basically have a refrigerant filling >12kg. In
order to avoid the declaration as dangerous goods also for these types, the option Refill cartridge
R410A (accessories) (see chapter 3.25) can be ordered. Following the performance check in the
factory, a quantity of refrigerant is filled in a certified refrigerant cylinder so that the 12kg limit is
kept to in the unit. The refill cartridge is then delivered together with the unit. The refrigerant
quantity drained for transport can be returned to the system as part of the commissioning using
the summary description provided with the refill cartridge.
5.2. Transport
The chiller may only be transported using a fork lift truck or crane with sufficient rated capacity.
The net weight of your machine is given in the technical data. Please note that if a machine has
already been in operation, it can contain residual fluids, which increase the transport weight.