4.8. Residual risks
4.8.1. Electrical
If all safety provisions are complied with there is no risk.
4.8.2. Mechanical
If all safety provisions are complied with there is no risk.
Mechanical damage to components or pipes of the refrigerant circuit can cause refrigerant to
leak. Leaking refrigerant can cause cold burns.
4.8.3. Chemical
4.8.4. Other
4.9. Dangerous substances
4.9.1. Refrigerant R410A
First aid measures:
▪ After inhaling: remove victim to fresh air, ensuring your own safety, and keep the person
at rest in a comfortable position. Get medical attention. If the person stops breathing,
give artificial respiration.
▪ Following skin contact: leave clothing that has fused with the skin. Rinse areas damaged
by cold with lukewarm water (never use hot water). Do not rub! Cover with sterile
dressing. Ensure medical treatment is provided.
ATTENTION! Toxic and caustic products are produced by the thermal
decomposition of the R410A refrigerant.
ATTENTION! Risk of suffocation if the chiller is installed in a room that is too
small. Please note and follow Chapter 6.2.2.
ATTENTION! In the EU you must follow the provisions of EN378-3. Please also
note and follow the local installation regulations and provisions, especially the
Ordinance on handling water pollutant substances and BGR500 Chapter 2.35.