Section 2
Installation
20412922
8-2012/Rev 10
2-5
Table 2-3
Ampacity and Power Voltage Requirements
Power Voltage
Motor
Horsepower
Full Load
Amps
Circuit Breaker
Amps
230/3/60 50 116 150
380/3/50 50 69 100
400/3/50 50 66 100
415/3/50 50 64 100
460/3/60 50 58 80
575/3/60 50 52 70
230/3/60 60 140 175
380/3/60 60 86 125
460/3/60 60 70 90
200/3/50-60 100 248 350
200-208/3/50-60 100 248/242 350
230/3/60 100 218 300
400/3/50 100 124 175
415/3/50 100 121 175
460/3/60 100 109 175
575/3/60 100 99 125
2.5 Service Connections
The intensifier requires two incoming water sources, cooling water and cutting water; two drain
lines, cooling water and wastewater; a high pressure discharge line, and an air supply line. All
piping must comply with local, regional and national codes.
Thoroughly purge all supply plumbing prior to connection to remove any residue
that could contaminate the system.
All service connections are made on the rear bulkhead of the machine as shown in Figure 2-3,
Service Connections. Table 2-4 lists the fittings required and the height of each interface
connection.
With the exception of the wastewater and contaminated waste drain lines, manual shutoff valves
should be installed for all connections. To facilitate service, the valves should be located as close
as practical to the interface connection.