Electrical installation
Important notes
6
l
152
EDS84ASC552 EN 8.1
6 Electrical installation
6.1 Important notes
{ Danger!
Hazardous electrical voltage
Depending on the device, all power connections remain live up to 3 minutes
after the mains has been switched off.
Possible consequences:
ƒ Death or severe injuries when touching the power terminals.
Protective measures:
ƒ Wait for at least 3 minutes before working on the power terminals.
ƒ Make sure that all power terminals are deenergised.
{ Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when the device is touched in the event of a fault.
Protective measures:
ƒ Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor diameter
10 mm
2
or PE conductor must be connected twice)
( Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
ƒ Destruction of the device if the mains voltage is too high.
Protective measures:
ƒ Observe the maximally permissible mains voltage.
ƒ Fuse the device correctly on the supply side against mains fluctuations and
voltage peaks.