Electrical installation
Devices in a power range of 30 ... 45 kW (3/PE AC 400 V)
Terminal assignment of the power connections
6
l
201
EDS84ASC552 EN 8.1
Connection of external brake resistor
Terminal X105 Labelling Description
Rb1, Rb2 Brake resistor
"
Functional earth
HF−shield termination by connection to PE
8400GG097b
Terminal data PE
Conductor
cross−section
Tightening
torque
!
Conductor
cross−section
Tightening
torque
!
[mm
2
]
[AWG]
[Nm]
[lb−in]
[mm
2
]
[AWG]
[Nm]
[lb−in]
E84AVxxx3034
E84AVxxx3734
E84AVxxx4534
16 ... 50
6 ... 0
4.0
35
Inbus
SW 4
2.5 ... 25
12 ... 2
4.0
35
PZ 2
7 x 1
, Please read the information on how to install and connect the brake resistor in
the corresponding mounting instructions.