EDS84ASC552 EN 8.1
Test steps Cable length See
1. Total cable length at 125 kbps: 600 m From Tab. 6−1
2. Segment cable length for 28 nodes and a cable cross−section of
0.5 mm
2
:
360 m From Tab. 6−2
3. Comparison: The value in point 2 is lower than the cable length of 450 m which must be implemented.
Result
ƒ Use of repeaters
Without the use of repeaters, a cable length of 450 m cannot be implemented.
After 360 m (point 2), a repeater must be used.
The Lenze repeater, type 2176 is used (cable reduction: 30 m).
ƒ Calculation of the max. cable length:
First segment: 360 m
Second segment: 360 m (acc. to Tab. 6−1)
minus 30 m (cable reduction if a repeater
is used)
Max. cable length that can be implemented if a repeater is used: 690 m.
Hence, the selected cable length can be implemented.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Table of Contents