Braking operation
Braking operation with external brake resistor
Operation at rated mains voltage 400 V
8
l
241
EDS84ASC552 EN 8.1
8.2.2 Operation at rated mains voltage 400 V
Switching threshold V
BRmax
: 725 V, adjustable
R
Bmin
[]
I
BRmax
[A]
P
BRmax
[kW]
I
BRd
[A]
P
Bd
[kW]
t
Z
[s]
t
on
[s]
t
fp
[s]
Type
E84AVxxx3714 390
1.9 1.3 1.9 1.3 − −
E84AVxxx5514 390 1.9 1.3 1.9 1.3 − −
E84AVxxx7514 390 1.9 1.3 1.9 1.3 − −
E84AVxxx1124 180 4.0 2.9 4.0 2.9 − −
E84AVxxx1524 180 4.0 2.9 4.0 2.9 − −
E84AVxxx2224 150 4.8 3.5 4.8 3.5 − −
E84AVxxx3024xxS 82 8.8 6.4 8.8 6.4 − −
E84AVxxx3024xx0 82 8.8 6.4 8.8 6.4 − −
E84AVxxx4024 47 15.4 11.2 13.0 9.4 − −
E84AVxxx5524 47 15.4 11.2 13.0 9.4 − −
E84AVxxx7524 27 26.9 19.5 26.9 19.5 − −
E84AVxxx1134 27 26.9 19.5 26.9 19.5 − −
E84AVxxx1534 18 40.3 29.2 40.3 29.2 − −
E84AVxxx1834 15 48.3 35.0 48.3 35.0 − −
E84AVxxx2234 15 48.3 35.0 48.3 35.0 − −
E84AVxxx3034 7.5 96.7 70.1 96.7 70.1 − −
E84AVxxx3734 7.5 96.7 70.1 96.7 70.1 − −
E84AVxxx4534 7.5 96.7 70.1 96.7 70.1 − −
R
Bmin
Minimum brake resistance, nominal value ±10 %
I
BRmax
Peak current
P
BRmax
Peak braking power
I
BRd
Continuous current RMS − important for the dimensioning of the cables
P
Bd
Continuous braking power
t
Z
Cycle time, periodic load change with running time and recovery time
t
on
Running time
t
Z
− t
on
Recovery time
t
fp
Maximum running time without initial load and compliance with the recovery
time