Electrical installation
HighLine C control terminals
Analog inputs and outputs
6
l
222
EDS84ASC552 EN 8.1
6.8.2 Analog inputs and outputs
X3
GND-A
X3
A2I
O2I
A2U
O2U
A1I
O1I
A1U
O1U
AR
GA
+10 V /
10 mA
0...10V
1k ... 10k
0 ... 10 V
"
8400HLC034 8400HLC012
Fig. 6−38 Connection of the analog inputs and outputs
Labelling Description
Controller Reference voltage 10 V
A1U
Analog voltage input 1
10 V
^ 80
A1I
Analog current input 1
0 ...+20 mA/+4 ...+20 mA
A2U
Analog voltage input 2
10 V
A2I
Analog current input 2
0 ...+20 mA/+4 ...+20 mA
GA GND analog signals
O1U
Analog voltage output 1
0 ... +10V
^ 80
O1I
Analog current output 1
0 ...+20 mA/+4 ...+20 mA
O2U
Analog voltage output 2
0 ... +10V
O2I
Analog current output 2
0 ...+20 mA/+4 ...+20 mA
Terminal data
Conductor cross−section Tightening torque
!
[mm
2
] [AWG] [Nm] [lb−in]
Flexible
0.2 ... 1.5
24 ... 16
With wire end ferrule
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com