EasyManua.ls Logo

Lenze 8400 HighLine C - Page 188

Lenze 8400 HighLine C
286 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation
Devices in the power range 0.37 ... 22 kW (3/PE AC 400 V)
Terminal assignment of the power connections
6
l
188
EDS84ASC552 EN 8.1
Connection to the DC bus (+U
G
, −U
G
)
Terminal X100 Labelling Description
PE
+UG
−UG
Alternative connection of the DC−bus voltage
PE Connection for the PE conductor
8400GGx001b
Terminal data PE
Conductor
cross−section
Tightening
torque
!
Conductor
cross−section
Tightening
torque
!
[mm
2
]
[AWG]
[Nm]
[lb−in]
[mm
2
]
[AWG]
[Nm]
[lb−in]
E84AVxxx3714
E84AVxxx5514
E84AVxxx7514
E84AVxxx1124
E84AVxxx1524
E84AVxxx2224
E84AVxxx3024xxS
1 ... 2.5
18 ... 12
0.5
4.4
3.5 x 0.6
1 ... 6
18 ... 10
1.7
15
PZ 2
7 x 1
E84AVxxx3024xx0
E84AVxxx4024
E84AVxxx5524
1 ... 6
18 ... 10
0.5
4.4
3.5 x 0.6
2.5 ... 16
12 ... 6
3.4
30
PZ 2
7 x 1
E84AVxxx7524
E84AVxxx1134
E84AVxxx1534
1 ... 16
18 ... 6
1.2
10.6
5.5 x 1
2.5 ... 16
12 ... 6
3.4
30
PZ 2
7 x 1
E84AVxxx1834
E84AVxxx2234
1.5 ... 25
16 ... 2
3.5
31
6.5 x 1
2.5 ... 25
12 ... 2
4.0
35
PZ 2
7 x 1
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com