Electrical installation
Devices in the power range 0.37 ... 22 kW (3/PE AC 400 V)
Terminal assignment of the power connections
6
l
190
EDS84ASC552 EN 8.1
Motor temperature monitoring
) Note!
In the Lenze setting, motor temperature monitoring is activated! In the
delivery status, there is a wire jumper between the terminals X106/T1 and
X106/T2. Before connecting a thermal sensor, remove the wire jumper.
) Note!
– If the terminal X106 is used, e.g. to connect an external PTC thermistor or
a thermal contact, ensure at least one basic insulation to the motor or
mains potential to not restrict the protective separation of the control
terminals.
– The terminal X106 is connected to PE inside the device but cannot be used
for protective earth.
Terminal X106 Labelling Description
T1
T2
Motor temperature monitoring with PTC element
(type−A sensor, switching performance acc. to EN 60947−8 for
type−A tripping units) or thermostat
(NC contact).
Lenze setting: activated, error message
Setting in C00585
8400GG016b
Terminal data
Conductor cross−section Tightening torque
!
[mm
2
] [AWG] [Nm] [lb−in]
E84AVxxxxxxx 0.2 ... 1.5 24 ... 16 − − 2.5 x 0.4
I Tip!
For an easy removal of the wire jumper:
1. Cut the wire jumper with side−cutting pliers.
2. Overcome the spring pressure of the terminal with a screwdriver.
3. Remove both wire ends individually.