Electrical installation
Common control terminals
System bus connection (CANopen)
6
l
207
EDS84ASC552 EN 8.1
6.6.2.1 Wire CAN plug connector (X1) and ensure bus termination.
ƒ Wire CAN plug connector (X1).
Only install shielded bus cables to avoid interference injection.
Fix the bus cable connected to plug connector X1 to the shield sheet of the
controller.
ƒ Ensure bus termination.
Only required if the controller is the first or the last node of the CAN bus.
Activate the bus termination vis DIP switch "R".
Terminal data
Conductor cross−section Tightening torque
!
[mm
2
] [AWG] [Nm] [lb−in]
Flexible
0.2 ... 1.5
24 ... 16
With wire end ferrule
Specification of the bus cable
We recommend the use of CAN cables in accordance with ISO 11898−2:
CAN cable in accordance with ISO 11898−2
Cable type Paired with shielding
Impedance 120 (95 ... 140 )
Cable resistance/cross−section
Cable length 300 m 70 m/m / 0.25  0.34 mm
2
(AWG22)
Cable length 301  1000 m 40 m/m / 0.5 mm
2
(AWG20)
Signal propagation delay 5 ns/m
StateLine, HighLine
X1
CAN-Ground
X1
R
CL
CH
120Ω
CG
CAN-Low
CAN-High
EDS84AVxxxx
,
"
"
"
CL
CH
CG
dcba
64
32
16 8
4 21
Baud CAN Adress
O
N
8400HLC048 8400SLC041
Fig. 6−27 CANopen connection