Electrical installation
Common control terminals
System bus connection (CANopen)
6
l
209
EDS84ASC552 EN 8.1
6.6.2.2 Structure of the CAN network
Master
Slave 1 Slave n
X1 X1 X
1
8400CAN006
Fig. 6−29 Wiring of system bus (CAN)
Bus cable length
) Note!
ƒ The permissible cable lengths must be observed.
ƒ Please observe the reduction of the total cable length due to the signal delay
of the repeater, see example below ( 210).
ƒ During mixed operation, multiple nodes are operated on one mains.
ƒ If the respective total cable lengths of the nodes differ at the same baud
rate, the lower value must be used for the determination of the max. cable
length.
Total cable length
1. Check whether the total cable length is complied with.
The total cable lenth is determined by the baud rate:
Baud rate [kbps] Max. bus length [m]
10 (not supported at the moment) 8075
20 4013
50 1575
125 600
250 275
500 113
800 (HighLine and TopLine,
StateLine from FW V11.0)
38
1000 (HighLine and TopLine,
StateLine from FW V11.0)
13
Tab. 6−1 Total cable length