Technical data
General data and operating conditions
4
29
EDS84ASC552 EN 8.1
Requirements on the motor cable
Capacitance per unit length
1.5 mm
2
/AWG 16 C
Core/core
/C
Core/shield
75/150 pF/m
2.5 mm
2
/AWG 12 C
core/core
/C
Core/shield
100/ 150 pF/m
Electric strength
VDE 0250-1 U
0
/U = 0.6/1.0 kV
(U
0
= r.m.s. value external - conductor/PE,
U = r.m.s. value - external conductor/external conductor)
UL U 600 V (U = r.m.s. value external conductor/external conductor)
Motor cable lengths without considering EMC limit values
Maximum motor cable length
1)
, (shielded)
U
rated
P
rated
after switching frequencies
[V] [kW] 4[kHz] 8[kHz] 16 [kHz]
230 0.25 ... 2.2 50 m 50 m 50 m
400 0.37 ... 2.2 50 m 50 m 25 m
500 0.37 ... 2.2 50 m 25 m 15 m
2)
400/500 3...15 50 m 50 m 50 m
400/500 18.5 ... 45 100 m 100 m 100 m
1)
If EMC conditions must be complied with, the permissible cable lengths may be shorter.
2)
At ambient temperatures of over4C,only13marepermissible.
Motor cable lengths with interference suppression
Compliance with category C2 (industry), cable-guided
Motor cable length (shielded)
after interference suppression and required earth-leakage circuit breaker
U
rated
P
rated
Integrated With SD filter With LD filter With LD and si-
nusoidal filter
[V] [kW] 30 mA FI 300 mA FI 30 mA FI without FI 300 mA FI without FI without FI
230 0.25 ... 2.2 25 m - 25 m 25 - 50 m 25 - 50 m - 50 - 100 m
400/500 0.37 ... 2.2 25 m - 25 m
1)
25 - 50 m
1)
25 - 50 m
1)
- 50 - 100 m
400/500 3.0 ... 15 - 25 m 25 m 25 - 50 m 25 - 50 m - 50 - 100 m
400/500 18.5 ... 45 - 25 m - - - 50 - 100 m -
1)
Observe switching frequency-dependent restrictions according to table ”Motor cable lengths without considering EMC
limit values”
Device-dependent filter assignments: See chapter ”Accessories”, 11.3 and 11.4
Compliance with category C1 (residential areas, public systems), cable-guided
Motor cable length (shielded)
after interference suppression and required earth-leakage circuit breaker
U
rated
P
rated
With LL filter With SD filter With LD filter
[V] [kW] 30 mA FI 30 mA FI 300 mA FI
230 0.25 ... 2.2 5m 25 m 50 m
400/500 0.37 ... 2.2 - 25 m
1)
50 m
1)
400/500 3.0 ... 15 - 25 m 50 m
400/500 18.5 ... 45 - - -
1)
Observe switching frequency-dependent restrictions according to table ”Motor cable lengths without considering EMC
limit values”
Device-dependent filter assignments: See chapter ”Accessories”, 11.3 and 11.4
If LL filters are used, the fault current is 3.5 mA. Fixed installation is not required.