4.2.5 Operation with increased power at a 230 V mains
The controller can be operated with increased continuous power (120% P
aN
) on a more
powerful motor. The overload capacity remains constant as if operated with a continuous
power of 100%; the information about the percentage values provided for the overload
phases still refers to rated data of 100%. Typical application cases include drives for units
with quadratic load characteristics such as pumps and fans.
) Note!
Operation with increased power is only permitted ...
ƒ With the rated data provided for the controller.
ƒ In the stated mains voltage range.
ƒ At switching frequencies of 2 kHz and 4 kHz.
ƒ At a max. ambient temperature of 40 °C.
ƒ With the stated installation types.
ƒ With the fuses, cable cross−sections, mains chokes and filters required for
this type of operation.
ƒ After parameterisation acc. to specification (cp. software manual
EDS84AV...)
Basis of the data
Mains Voltage Voltage range Frequency range
U
Lrated
[V] U
Lrated
[V] f [Hz]
1/N/PE AC 230 180 − 0 % ... 264 + 0 % 45 − 0 % ... 65 + 0 %
Mains current at I
aN
Apparent output power Motor power
with external
mains choke
without external
mains choke
U, V, W 4 pol. ASM
Type I
LR
[A] I
LR
[A] S
aR
[kVA] P
aR
[kW]
E84AVxxx2512 3.6 4.1 0.8 0.37
E84AVxxx3712 5.0 − 1.0 0.55
E84AVxxx5512 6.0 6.4 1.3 0.75
E84AVxxx7512 8.4 − 1.7 1.1
E84AVxxx1122 11.9 14.4 2.4 1.5
E84AVxxx1522 13.7 − 3.0 2.2