Technical data
Rated data
Operation with increased power at a 400 V mains
4
l
56
EDS84ASC552 EN 8.1
4.2.6 Operation with increased power at a 400 V mains
The controller can be operated with increased continuous power (120% P
aN
) on a more
powerful motor. The overload capacity remains constant as if operated with a continuous
power of 100%; the information about the percentage values provided for the overload
phases still refers to rated data of 100%. Typical application cases include drives for units
with quadratic load characteristics such as pumps and fans.
) Note!
Operation with increased power is only permitted ...
ƒ With the rated data provided for the controller.
ƒ In the stated mains voltage range.
ƒ At switching frequencies of 2 kHz and 4 kHz.
ƒ At a max. ambient temperature of 40 °C.
ƒ With the stated installation types.
ƒ With the fuses, cable cross−sections, mains chokes and filters required for
this type of operation.
ƒ After parameterisation acc. to specification (cp. software manual
EDS84AV...)
Basis of the data
Mains Voltage Voltage range Frequency range
U
Lrated
[V] U
Lrated
[V] f [Hz]
3/PE AC 400 320 − 0 % ... 440 + 0 % 45 − 0 % ... 65 + 0 %