Technical data
Rated data
Operation with increased power at a 400 V mains
4
l
60
EDS84ASC552 EN 8.1
Operation with external mains choke/mains filter
Type Installation according to EN 60204−1
1)
Installation according
to UL
2)
FI
3)
L1, L2, L3 − Laying system L1, L2, L3
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [A] [AWG] [mA]
E84AVxxx3714 C 6 6 1.0 6 18
30
3)
E84AVxxx5514 C 6 6 1.0 6 18
E84AVxxx7514 C 6 6 1.0 6 18
E84AVxxx1124 C 6 6 1.0 10 16
30
3)
E84AVxxx1524 C 6 6 1.0 10 16
E84AVxxx2224 C 10 10 1.5 10 16
E84AVxxx3024xxS C 10 10 1.5 15 14 300
3)
E84AVxxx3024xx0 C 10 10 1.5 15 14 300
3)
E84AVxxx4024 C 16 16 2.5 20 12
300
3)
E84AVxxx5524 C 20 20 4 20 12
E84AVxxx7524 C 20 20 4 2.5 20 12
300
3)
E84AVxxx1134 C 32 32 10 10 30 10
E84AVxxx1534
E84AVxxx1834 C 50 50 16 60 6
300
3)
E84AVxxx2234 C 63 63 25 60 6
E84AVxxx3034 C100 100 25 80 4 300
3)
E84AVxxx3734 C125 125 50 100 3
300
3)
E84AVxxx4534 C125 125 50 125 1
1)
These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298−4). The cable cross−sections apply under the following conditions: Use of PVC−insulated copper cables,
conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
Use UL−approved cables, fuses and fuse holders only.
UL fuse: voltage 500 V, tripping characteristic for example "H", "K5" or "CC". The cable cross−sections apply under
the following conditions: conductor temperature < 75 °C, ambient temperature < 45°C.
3)
Universal−current sensitive earth−leakage circuit breaker, short−time delay
If cables are longer than 50 m, the protective circuit−breaker may respond, depending on the cable type and
switching frequency.
Circuit breaker
Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category
Fuse
Observe national and regional regulations