Technical data
StateLine C control terminals
External supply voltage 24 V
4
l
76
EDS84ASC552 EN 8.1
4.6 StateLine C control terminals
4.6.1 External supply voltage 24 V
Labelling Feature Rated value
X4/24E
Connection for external 24 V supply
voltage by a safely separated
power supply unit (required for
mains−independent supply of the
control electronics and the
communication module)
24 V in accordance with IEC 61131−2
19.2 ... 28.8 V
Residual ripple max. 5 %
SELV/PELV
Suppression of voltage pulses Suppressor diode 36 V, bidirectional
Polarity reversal protection When polarity is reversed: no function and no
destruction
Current consumption
Approx. 0.6 A during operation
Max. 1.5 A starting current for 100 ms
Capacity to be charged 1000 F
X4/GIO GND, reference potential for digital signals
Labelling Feature Rated value
X4/24I
24 V voltage output
to connect digital inputs via
potential−free contacts
External supply at 24E: voltage drop < 2.5 V
Internal supply: DC 18 ... 28 V
Max. output current 50 mA
Electric strength of external voltage +30 V
Excess current release Automatically resettable
X4/GIO GND, reference potential for digital signals