Display code Short designaon Default seng Seng range Address Category
P431.11 Min. torque 0.0 % -400.0 ... 400.0 % 0x2637:011 general
P431.12 Max. torque 100.0 % -400.0 ... 400.0 % 0x2637:012 general
P440.xx Analog output 1
P440.01 AO1 outp. range 0 ... 10 VDC [1] Selecon list 0x2639:001 general
P440.02 AO1 funcon Outp. frequency [1] Selecon list 0x2639:002 general
P440.03 AO1 min. signal 0 -2147483648 ... 2147483647 0x2639:003 general
P440.04 AO1 max. signal 1000 -2147483648 ... 2147483647 0x2639:004 general
P450.xx Freq. presets
P450.01 Freq. preset 1 20.0 Hz 0.0 ... 599.0 Hz 0x2911:001 general
P450.02 Freq. preset 2 40.0 Hz 0.0 ... 599.0 Hz 0x2911:002 general
P450.03 Freq. preset 3 Device for 50-Hz mains:
50.0 Hz
Device for 60-Hz mains:
60.0 Hz
0.0 ... 599.0 Hz 0x2911:003 general
P450.04 Freq. preset 4 0.0 Hz 0.0 ... 599.0 Hz 0x2911:004 general
P450.05 Freq. preset 5 0.0 Hz 0.0 ... 599.0 Hz 0x2911:005 general
P450.06 Freq. preset 6 0.0 Hz 0.0 ... 599.0 Hz 0x2911:006 general
P450.07 Freq. preset 7 0.0 Hz 0.0 ... 599.0 Hz 0x2911:007 general
P450.08 Freq. preset 8 0.0 Hz 0.0 ... 599.0 Hz 0x2911:008 general
P450.09 Freq. preset 9 0.0 Hz 0.0 ... 599.0 Hz 0x2911:009 general
P450.10 Freq. preset 10 0.0 Hz 0.0 ... 599.0 Hz 0x2911:010 general
P450.11 Freq. preset 11 0.0 Hz 0.0 ... 599.0 Hz 0x2911:011 general
P450.12 Freq. preset 12 0.0 Hz 0.0 ... 599.0 Hz 0x2911:012 general
P450.13 Freq. preset 13 0.0 Hz 0.0 ... 599.0 Hz 0x2911:013 general
P450.14 Freq. preset 14 0.0 Hz 0.0 ... 599.0 Hz 0x2911:014 general
P450.15 Freq. preset 15 0.0 Hz 0.0 ... 599.0 Hz 0x2911:015 general
P451.xx PID presets
P451.01 PID preset 1 0.00 PID unit -300.00 ... 300.00 PID unit 0x4022:001 general
P451.02 PID preset 2 0.00 PID unit -300.00 ... 300.00 PID unit 0x4022:002 general
P451.03 PID preset 3 0.00 PID unit -300.00 ... 300.00 PID unit 0x4022:003 general
P451.04 PID preset 4 0.00 PID unit -300.00 ... 300.00 PID unit 0x4022:004 general
P451.05 PID preset 5 0.00 PID unit -300.00 ... 300.00 PID unit 0x4022:005 general
P451.06 PID preset 6 0.00 PID unit -300.00 ... 300.00 PID unit 0x4022:006 general
P451.07 PID preset 7 0.00 PID unit -300.00 ... 300.00 PID unit 0x4022:007 general
P451.08 PID preset 8 0.00 PID unit -300.00 ... 300.00 PID unit 0x4022:008 general
P452.xx Torque presets
P452.01 Torque preset 1 100.0 % -400.0 ... 400.0 % 0x2912:001 general
P452.02 Torque preset 2 100.0 % -400.0 ... 400.0 % 0x2912:002 general
P452.03 Torque preset 3 100.0 % -400.0 ... 400.0 % 0x2912:003 general
P452.04 Torque preset 4 100.0 % -400.0 ... 400.0 % 0x2912:004 general
P452.05 Torque preset 5 100.0 % -400.0 ... 400.0 % 0x2912:005 general
P452.06 Torque preset 6 100.0 % -400.0 ... 400.0 % 0x2912:006 general
P452.07 Torque preset 7 100.0 % -400.0 ... 400.0 % 0x2912:007 general
P452.08 Torque preset 8 100.0 % -400.0 ... 400.0 % 0x2912:008 general
P500.xx Module ID
P500.01 Acve module ID - - (Read only) 0x231F:001 general
P500.02 Module ID conn. - - (Read only) 0x231F:002 general
P505.xx NetWordIN1 fct.
P505.01 NetWordIN1.00 Not acve [0] Selecon list 0x400E:001 general
P505.02 NetWordIN1.01 Not acve [0] Selecon list 0x400E:002 general
P505.03 NetWordIN1.02 Quick stop [3] Selecon list 0x400E:003 general
P505.04 NetWordIN1.03 Not acve [0] Selecon list 0x400E:004 general
P505.05 NetWordIN1.04 Run forward [8] Selecon list 0x400E:005 general
P505.06 NetWordIN1.05 Setp: Preset b0 [18] Selecon list 0x400E:006 general
* Default seng depending on the size. Firmware version 05.00.00.00