Page 38
For output types, the current setting is shown on the bottom line. Press the ' # ' key to select a new type from a list of
types. The display shows:
SELECT TYPE: 6
INT SNDR
Use the Up and Down arrow keys to scroll through the list, or select the appropriate output type number, and then
press ' # ' to enter the new type.
If the Interior Horn is configured as a "General Purpose" output, Unit Number 41 is used to control the output. If the
Exterior Horn is configured as a "General Purpose" output, Unit Number 42 is used to control the output. In this
configuration, Unit Numbers 41 and 42 should not be used as "Flags".
Z-WAVE NODE ID
The Node ID is a unique number between 1 and 232 which identifies a Z-Wave device on the Vizia RF Z-Wave
Network. Each Node must be associated (mapped) with a unit number in the Omni LTe controller.
For Vizia RF Z-Wave Wall Controllers, enter the Node ID for the Z-Wave Wall Controller associated with that room
(e.g. Unit 1, Unit 9, Unit 17, or Unit 25). If desired, more than one Wall Controller may be assigned to a room by
associating the Wall Controller on any unit number in that room. If a second Wall Controller is used, do not assign in
a name in the controller.
UNIT 1 NODE ID: 0
0-232
THROUGH
UNIT 32 NODE ID: 0
0-232 ↑
Enter the Node ID (0-232) for each Z-Wave device followed by the ' # ' key.
Enter 0 if there is no node associated with the specified unit number.
SETUP ZONES
To configure wireless receivers, zone resistors, and the zone types (definitions) for each security zone, from the
Installer Setup menu, select the 2 (ZONE) key.
Note: There are zone options that define the way that each zone functions. To access Zone Options, press the 8
(ZOPT) key.
WIRELESS RECEIVER
A Wireless Receiver can be used to add 16 zones (17-32) to the Omni LTe. If used, you must enable the following
item:
WIRELESS RECEIVER: 0
0=NO 1=YES
↓
ZONE RESISTORS
This item is used to specify if the 1000-ohm end-of-line zone resistors will be used with zone inputs other than
Supervised Fire and Gas. If this item is set to "Yes", all zones will require an end-of-line resistor.
The default setting is "Yes".
ZONE RESISTORS: 1
0=NO 1=YES