SIA CP-01 COMPLIANCE
This control complies with the SIA CP-01 Control Panel Standard - Features for False Alarm Reduction.
CP-01 is a standard sponsored by the Security Industry Association (SIA) designed with features for security systems
and associated arming and disarming devices intended to reduce the incidence of false alarms.
PROGRAMMABLE FEATURES
SHIPPING DEFAULTS AND RECOMMENDED PROGRAMMING
FEATURE
CP-01
PAR. #
REQUIREMENT
RANGE
SHIPPING
DEFAULT
RECOMMENDED
PROGRAMMING*
Exit Time
(Exit Delay)
4.2.2.1
Required
(programmable)
For full or auto arming: 45-
180 seconds
60 seconds
60 seconds
Progress Annunciation - Disable
(Audible Exit Delay)
4.2.2.2
Allowed
Individual consoles may be
disabled
Enabled on
all consoles
Enabled on all
consoles
Exit Time Restart
4.2.2.3
Required Option
For re-entry during exit
delay
Enabled
Enabled
Unvacated Premises
4.2.2.5
Required Option
(except for remote arm)
If no exit after full arm
Enabled
Enabled
Entry Delay
4.2.3.1
Required
(programmable)
30-60 seconds
30 seconds
At least 30 seconds**
Abort Window for Non-Fire Zones
(Dial Out Delay – Zone Option)
4.2.5.1
Required Option
May be disabled by zone
Enabled
Enabled (all zones)
Abort Window Time
(Dial Out Delay)
4.2.5.1
Required Option
15-45 seconds
30 seconds
At least 15 seconds**
Abort annunciation
(Alarm Aborted)
4.2.5.1.2
Required Option
Display that alarm was
aborted
Enabled
No programming
option
Cancel Window
(Alarm Reset Time)
4.2.5.4
Required
6-30 minutes
6 minutes
At least 6 minutes
Cancel annunciation
(Alarm Canceled)
4.2.5.4.1
Required Option
Display that alarm was
canceled
Enabled
No programming
option
Duress Feature
(Duress Code)
4.2.6.1 &
4.2.6.2
Allowed Option
No duplicates with other
user codes
Disabled
Disabled
Cross Zoning
(Cross Zoning – Zone Option)
4.3.1
Required Option
May be enabled by zone
Disabled
Enabled and two (or
more) zones
programmed
Programmable Cross Zoning Time
(Cross Zone Window)
4.3.1
Allowed
15-120 seconds
15 seconds
Time based on walk
path in protected area
Swinger Shutdown
(Swinger Shutdown Number)
4.3.2
Required
(programmable)
For all non-fire zones, shut
down at 1 or 2 trips
One trip
One trip
Swinger Shutdown Disable
(Swinger Shutdown – Zone
Option)
4.3.2
Allowed
For non-police response
zones
Enabled
Enabled (all zones)
Fire Alarm Verification
4.3.3
Required Option
Depends on Sensors
Disabled
Enabled unless
sensor can self verify
Call Waiting Cancel
4.5
Required Option
Depends on user phone line
Disabled
Enabled if user has
call waiting
* Programmable at installation may be subordinate to other UL requirements for the intended application.
** Combined Entry Delay and Abort Window (Dial Out Delay) should not exceed 1 minute.
Minimum Equipment Requirements for a CP-01 Compliant Installation:
Quantity
Description
Applicable Model Numbers
1
Omni LTe Controller
Model 20A00-70, 20A00-72, 20A00-73
1 - 8
Omni Console
Model 33A00-1, 33A00-4
WEB VERSION